Solar String Fusing Calculator

South West Tech — do your strings need fuses, and what rating?

TRADE GUIDE — VERIFY AGAINST AS/NZS 5033 & DATASHEET
Both values are on the module datasheet. Strings on separate MPPT inputs don't combine — count only strings paralleled together.
—
Possible back-feed into a faulted string—
Module reverse current limit—
Fuse rating window (1.5–2.4 × Isc)—
Suggested standard gPV fuse—
Minimum string cable rating—
Fuse voltage rating required—
Method: back-feed = (strings − 1) × 1.25 × Isc; fuses required where this exceeds the module's max series fuse rating. Fuse window per AS/NZS 5033: ≥1.5 × Isc, ≤2.4 × Isc and ≤ module max series fuse rating; fuse BOTH polarities with gPV (IEC 60269-6) fuses rated ≥ maximum PV array voltage. String cable must carry the fuse rating (or 1.25 × combined backfeed where unfused). Guide only — the installing electrician must verify against AS/NZS 5033 and the module datasheet. South West Tech — 0488 224 284.